Description
This Field Bus Coupler connects the WAGO I/O system as a slave with the DeviceNet fieldbus.
The Bus Coupler detects all configured I/O terminals and creates a local process image. This can be a mixed anordnug of analogue (Data Exchange word-by-word) and digital (Data Exchange bit-by-bit) terminals.
Via the DeviceNet fieldbus is the image in the memory of the responsible control is displayed.
The local process image is divided into a input and output data area. The process data can be read via the devicenet and in a control processed. The process output data are output via the devicenet.
The data of the analog terminals are used in the order of their position after the bus coupler in the automatically created process image is stored. The bits of the digital terminals are used to bytes are joined and the analogue data is appended. Is the number of digital I/O bit larger than 8, the coupler automatically another byte.
N.B.:
Caution: Configuration Files (EDS) required!