Overview
Low resistance, continuity, insulation resistance, line impedance, loop impedance
Testing of FI/RCD circuit breakers standard and delayed (S), type AC, A, F, B, B+
TRUE RMS voltage, frequency, rotating field, First fault leakage current in the IT network
measured value memory over 4 levels (object, block, fuse, measuring point) for 1800 measurements
Upload of system structures and download of measured values
Bidirectional interfaces (USB/ RS 232)
Description
Safety tests on electrical systems after installation, modification or as regular repeat tests according to VDE 0100/ 0105 and IEC 60364 can be carried out easily and efficiently with the BENNING IT 130. In addition, the standard and delayed (S) AC, A, F, B, B+ FI/ RCD circuit breakers can be tested with auto test, touch voltage, trip time and trip current (ramp test).
Characteristics
For the testing of electric systems according to DIN VDE 0100-600 and DIN VDE 0105-100, including Testing of FI/RCD protection switch Type B/B+
Facilities: illuminated graphic display with help function and connection diagram · Measurement function can be selected directly via rotary switch · Rotary field · The first error leakage current in the IT system · Measurement results with symbols for passed/not passed · Measured value memory via 4 levels (object, Block, Fuse, measuring point) · Integrated real-time clock · Upload of plant structures, download of the measurement values. · Bi-directional USB/RS 232 interface · Green/Red LED for good/bad display on the test device/Commander test tip · Commander probe tip with test/MEMORY button, LED measuring point lighting · Software for easy reading download, logging (Test Report/ZVEH test protocol), creation and transmission (upload) of plant structures for BENNING IT 130 · Online voltage monitor · Optional: Earthing, current, luminosity measurement.
Technical data: Display: LCD graphic display · Measurement range - low resistance 0.01 Ohm - 2 kOhm · Test current 200 mA · Reading range - Insulation resistance: 10 kOhm - 1 GOhm · Test voltage 50/100/250/500/1000 V · Measuring range line (L-N/L) and loop impedance measurement (L-PE): 0.01 Ohm - 10 kOhm · Measuring range Short circuit current: 0.01 A - 200 kA · FI/RCD testing type AC/A/F, B/B+: tripping time, tripping current (ramp), contact voltage, auto test · Voltage reading range: 1 - 550 V AC/DC TRMS · Frequency measuring range: 0 - 500 Hz · Measured value memory: 1800 Results · Power supply: 6 AA-size NiMH batteries
Delivery content
- Case
- PC software
- USB/RS 232 cable
- switchable Commander probe
- test cable with safety plug
- universal test cable
- 3 x probes/crocodile clips
- charger with batteries
- operating instructions
Keywords
04014651441033, 4014651441033, Benning, 044103-ISO, IT 130, bgv