Description
Maximum current 32A, standby loss only 0.4 watts. Series installation device for mounting on DIN-EN 60715 TH35 mounting rail. 1 division unit =18mm wide, 58mm deep. Accuracy class B (1%). With S0 interface. This AC meter measures the active energy based on the current flowing between the input and the output. The own consumption of only a maximum of 0.4 watt active power is not measured and not displayed. Like all counters without MID declaration of conformity in Europe, it is not approved for monetary electricity accounting. Every 30 seconds, the display switches from the active energy accumulated in kWh to the current consumption in watts for 5 seconds. 1 external conductor can be connected with a current of up to 32A. With an expected load of more than 50%, a ventilation distance of 1/2 division unit to adjacent devices must be observed. If necessary, use spacer DS12. The starting current is 20mA. The display can only be read with power supply. However, the consumption is stored in a non-volatile memory and is displayed again immediately after a power failure. Two N terminals for secure cross-wiring of several counters. The digital display has 7 digits. Up to 99999.99 kWh, two decimal places are displayed. From 100000,0kWh only one. The power consumption is indicated by a 1000 times per kWh flashing bar in the display. Error message: In the event of a connection error, an LED flashes on the display.